house electricians or people good with house wiring

M240Bravo

Well-Known Member
Established Member
Joined
Sep 30, 2007
Messages
4,586
Location
Yemen
So when built my lake house I put electric fireplaces in all bedrooms and living areas. Knowing what they run for power I ran single plug-ins with 14gq wires all ran to their own 15amp breaker.


Well last night a friends family was staying at the house, and they smelt something burning and I found this. Breaker didn't pop, it just melted the wire.
IMG_3764.JPG


Any reason the wire would caught fire and melt like that? I'm thinking of replacing all the fireplaces now.
 

blk02edge

Well-Known Member
Established Member
Joined
Feb 20, 2008
Messages
8,895
Location
BC
Likely the splice/connection. That is exactly what happens when a wire is loose. Do you have photo of where that wire was attached?
 

Buckwheat 1

I like Blm junk in my butt
Established Member
Joined
Sep 29, 2015
Messages
5,029
Location
Cape Cod
So when built my lake house I put electric fireplaces in all bedrooms and living areas. Knowing what they run for power I ran single plug-ins with 14gq wires all ran to their own 15amp breaker.


Well last night a friends family was staying at the house, and they smelt something burning and I found this. Breaker didn't pop, it just melted the wire.View attachment 1534315

Any reason the wire would caught fire and melt like that? I'm thinking of replacing all the fireplaces now.

Looks like the romex was sitting against the hot metal of the the fire place. Read the directions and make sure romex is suitable that portion of the heater. Also make sure the thermostat is turning on and off properly.


Sent from my iPhone using the svtperformance.com mobile app
 

M240Bravo

Well-Known Member
Established Member
Joined
Sep 30, 2007
Messages
4,586
Location
Yemen
Likely the splice/connection. That is exactly what happens when a wire is loose. Do you have photo of where that wire was attached?


you can see the piece that broke off on the under side of the wire. Its just one of those slip on plug things.
 

Bearbo

Well-Known Member
Established Member
Premium Member
Single Barrel Sirs
Joined
Oct 30, 2015
Messages
890
Location
Tennessee
Female terminal connector. Slip on plug thing, really.
 

blk02edge

Well-Known Member
Established Member
Joined
Feb 20, 2008
Messages
8,895
Location
BC
you can see the piece that broke off on the under side of the wire. Its just one of those slip on plug things.
oh I see that now, either way, a poor connection there was your problem. That is definitely heat from lack of being tight. Ive seen plenty of literally red hot connections, nothing to do with current load as a 9v battery can do that as well
 

1wild-horse

Purveyor of missed information
Established Member
Joined
Apr 4, 2009
Messages
3,399
Location
IA
No expert here, but 14ga sounds a little light for a load like an electric fireplace.
 

blk02edge

Well-Known Member
Established Member
Joined
Feb 20, 2008
Messages
8,895
Location
BC
No expert here, but 14ga sounds a little light for a load like an electric fireplace.
15a breakers though. If it was a problem they would be tripping. 14G gauge wire wont start melting like that at slightly excess current either way, load is not the issue (electrician for 11 years now).
 

1wild-horse

Purveyor of missed information
Established Member
Joined
Apr 4, 2009
Messages
3,399
Location
IA
15a breakers though. If it was a problem they would be tripping. 14G gauge wire wont start melting like that at slightly excess current either way, load is not the issue (electrician for 11 years now).
Was pretty sure the electricians used 12-2 for every outlet circuit in my house. Thought that was just A standard thing.
Arcing from a poor connection can definitely cause some heat though.
 

SVTdreamin04

What's a "Termi"???
Established Member
Premium Member
Joined
Sep 20, 2015
Messages
2,536
Location
America
Industrial Electrical Controls in a very wet environment is what I do for a living. That looks like either a loose connection causing damage over time or the wire for hot from environmental exposure for some reason. A loose connection can cause a loss of voltage which in turn will cause higher current.

I wouldn't replace all of your fireplaces, I would go thru and check all connections to make sure they are tight and check for any insulation damage. If you have any buddies that have access to a thermal camera, you can easily find loose connections by shooting the wiring with the thermal camera. Loose connections generate excess heat.


Sent from my iPhone using Tapatalk
 

quad

Well-Known Member
Established Member
Joined
Jun 1, 2004
Messages
8,073
Location
Detroit
No expert here, but 14ga sounds a little light for a load like an electric fireplace.
Yes I would have gone with 12 ga and 20A breakers. But the 15A breaker would trip if the load exceeded the rating. Running 14 ga with a 20A breaker would be the problem and not code compliant since the wire would be overloaded before the breaker could trip.

I agree it could be that the connection was not tight enough. I have a 20A outlet that melted with only a LED monitor plugged into it. Opened up the box and the neutral wire was melted where it attaches to the outlet. It must not have been tightened properly. Breaker never tripped. I replaced the melted outlet and made sure to tighten it properly. An electrician told me you can also tighten wires down more with a slotted (flat head) screwdriver than a Phillips head. He said he only uses slotted screwdrivers in electrical panels and to tighten down wires in outlets, light switches etc. Wire nuts also have to be tightened properly.
 

Revvv

Infinity Poster
Established Member
Joined
Dec 8, 2017
Messages
10,189
Location
GA
Looks like the romex was sitting against the hot metal of the the fire place. Read the directions and make sure romex is suitable that portion of the heater. Also make sure the thermostat is turning on and off properly.


Sent from my iPhone using the svtperformance.com mobile app
Listen to this man.

Sent from my SM-G900V using Tapatalk
 

blk02edge

Well-Known Member
Established Member
Joined
Feb 20, 2008
Messages
8,895
Location
BC
Was pretty sure the electricians used 12-2 for every outlet circuit in my house. Thought that was just A standard thing.
Arcing from a poor connection can definitely cause some heat though.
Very well could have but the standard is 14g in residential (20A counter plugs) but certain loads need to be properly spec'd and 12 in commercial. As a service electrician first thing I would do is re-do connection, and test current draw with my clamp on meter if I saw anything over 12A then id be suggesting replacing with 12g/20a or fireplace with something lesser.

Does not have to do with heat or overcurrent though as like I said breakers would be tripping. Nor does it have anything do do with the T-stat as it would be rated to run non stop anyway
 